Regulated DC Power Supplies - Bench Mounting

Model 3003, 3006, 3015, 3033

This series of low cost bench mounting power supplies includes four models with output voltage ranges of 0-30V dc or 0-60V dc in single or dual configuration. A 5V dc auxiliary supply is available on the model 3033 dual supply. Separate digital panel meters are provided for monitoring the output voltage and current simultaneously. Voltage is continually variable over the range with a COARSE control and an additional FINE control varies the output over 10% of the set value.

All models can be operated in either constant voltage or constant current mode. The dual supplies have a tracking mode available. A novel feature is a power saving device which selects a lower ratio of the main supply transformer secondary automatically if the output falls below around 50% of the maximum rated output voltage.

Each power supply comes complete with a 1.5 meter flexible input lead.


Model Output
Volts DC
Output
Current A
Dimensions
H x W x D
Weight kg
3003
3006
3015
3033
0 - 30
0 - 60
0 - (±)30
0 - (±)30
0 - 3.0
0 - 1.5
0 - 1.5
0 - 1.5
170 x 130 x 325
170 x 130 x 325
170 x 230 x 325
170 x 230 x 325
5.5
5.5
8.0
8.0
Note: Model 3033 has a 5V, 5A fixed auxiliary supply.

Specifications Model
3003
Model
3006
Model
3015
Model
3033
Output   DC Voltage
DC Current
0-30V
0-3A
0-60V
0-1.5A
0-±30V
0-±1.5A
0-±30V
0-±1.5A
Load Regulation   CV
(Load Effect) CC
0.02% + 2mV (max)
0.02% + 5mA (max)
Load Regulation   CV
(Source Effect) CC
0.02% + 2mV (max)
0.02% + 0.25mA (max)
Ripple & Noise   CV
  CC
0.2mV(rms), 4mV(p-p) (max)
0.2mA(rms), 4mA(p-p) (max)
Digital Panel Meters    
Digits & Resolution V
  A
 
3dgts(100mV)
3dgts(10mA)
Accuracy ±(0.5% rdg+1 dgt)
Tracking Error   N/A
  ±(0.5% + 10mV)
(max)
Fixed 5V/5A Output   V
  A
Ripple & Noise  
Line & Load Regulation  
N/A 5V ± 2.5%
5A ± 2.5%
<2m Vrms
0.1% + 5mV
Operating Temperature 0°C to 40°C
Storage Temperature -20°C to 60°C
Temperature Coefficient    
(after 30 minute warm up) V
  A
 
(0.05% + 2mV)/C (10 to 30°C) (max)
(0.1% + 2mA)/C (10 to 30°C) (max)
Drift (Stability)   V
(8hr, Interval) A
0.05% + 4mV (max)
0.1% + 4mA (max)
AC Input (± 10%, 110/220, 120/240), Single Phase 50-60Hz, Fused

Click here to enquire about this product | Amalgen Homepage


Amalgen Technologies Pty Ltd
43 Anderson Road,
Mortdale NSW 2223 Australia
Phone: +61 2 9570 2855
Fax: +61 2 9580 5128
 
© 2007 All rights reserved. Amalgen Technologies Pty Ltd.