DR-60 - 60 Watt Single Output Class II DIN Rail Power
|
![]() |
| Specifications | |
| Input voltage: | 88 ~ 264VAC; 124 ~ 370VDC |
| Output voltage: | Refer to table below |
| AC inrush current: | Cold start, 30A at 115VAC & 40A at 230VAC |
| Overload protection: | 105% ~ 165% foldback current limiting, auto recovery |
| Line/load regulation: | ±1.0% |
| Setup, rise & hold up time: | 100ms, 30ms, 60ms at 230V full load |
| Withstand time: | I/P ~ O/P: 3KV, I/P ~ FG: 1.5KV, 1 minute |
| Working temperature: | -20 ~ +45°C @100%, +60°C @ 60% load |
| Safety standard: | UL60950-1, TUV EN60950-1 approved |
| EMC standards | EN55022 class B, EN61000-3-2,3, EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3 |
| Connection: | I/P: 2 poles, O/P: 4 poles screw DIN terminal |
| Dimensions: | 78mm W x 93mm H x 56mm D |
| Weight: | 0.3 kg |
| Type No. | Output | DC voltage adjustment | Over Volts protection | R & N | Efficiency |
| DR-60-5 | 5V ±2%, 6.5A, 32.5W | 4.75 ~ 5.5 V | 5.75 ~ 6.75 V | 80mV p-p | 76% |
| DR-60-12 | 12V, ±1%, 4.5A, 54W | 11.1 ~ 13.2 V | 13.8 ~ 16.2 V | 120mV p-p | 83.5% |
| DR-60-15 | 15V, ±1%, 4.0A, 60W | 13.5 ~ 16.5 V | 17.25 ~ 20.25 V | 120mV p-p | 84.5% |
| DR-60-24 | 24V, ±1%, 2.5A, 60W | 21.6 ~ 26.4 V | 27.6 ~ 32.4 V | 150mV p-p | 86% |
| Click here to enquire about this product | Amalgen Homepage |
|
Amalgen Technologies Pty Ltd 43 Anderson Road, Mortdale NSW 2223 Australia Phone: +61 2 9570 2855 Fax: +61 2 9580 5128 |