DR-75 - 75 Watt Single Output DIN Rail Power
|
![]() |
| Specifications | |
| Input voltage: | 85 ~ 264VAC; 120 ~ 370VDC |
| Output voltage: | Refer to table below |
| AC inrush current: | Cold start, 30A at 115VAC & 60A at 230VAC |
| Overload protection: | 105% ~ 150% constant current limiting, auto recovery |
| Over volts protection: | 121% ~ 142% rated output voltage |
| Setup, rise & hold up time: | 1000ms, 60ms, 50ms at 230V full load |
| Withstand time: | I/P ~ O/P: 3KV, I/P ~ FG: 1.5KV, 1 minute |
| Working temperature: | -10 ~ +45°C @100%, +60°C @ 60% load |
| Safety standard: | UL508, TUV EN60950-1 approved |
| EMC standards | EN55022 class B, EN61000-3-2,3, EN61000-6-2, EN61000-4-2,3,4,5,6,8,11, ENV50204 |
| Connection: | I/P: 3 poles, O/P: 4 poles screw DIN terminal |
| Dimensions: | 100mm x 55.5mm x 125.2mm D |
| Weight: | 0.55 kg |
| Type No. | Output | DC voltage adjustment | R & N | Efficiency |
| DR-75-12 | 12V ±2%, 6.3A | 12 ~ 14V | 100mV p-p | 76% |
| DR-75-24 | 24V, ±1%, 3.2A | 24 ~ 28V | 150mV p-p | 80% |
| DR-75-48 | 48V, ±1%, 1.6A | 48 ~ 53V | 240mV p-p | 81% |
| Click here to enquire about this product | Amalgen Homepage |
|
Amalgen Technologies Pty Ltd 43 Anderson Road, Mortdale NSW 2223 Australia Phone: +61 2 9570 2855 Fax: +61 2 9580 5128 |