DRT-960 - 960W three phase DIN rail power
  • Input 340 ~ 550VAC, 3 phase 4 wires
  • UL508 listed
  • High efficiency up to 92%
  • Protections:short circuit / overload / over voltage / over temperature
  • Optional parallel function (1+1)
  • Installed on DIN rail TS35/7.5 or 15
  • EN61000-6-2 industrial immunity level
  • 100% full load burn-in test
  • Cooling by free air convection
  • 3 years warranty

Specifications
Input voltage: 340 ~ 550 VAC ; 3 phase 4 wires
Output voltage: Refer to table below
Inrush current: Cold start, 50A
Adjustment range: 24V : 24 ~ 28V, 48V : 48 ~ 55V
Overload protection: 105% ~ 125% output constant current limiting shut off after 3 sec., AC recycle restart
Over voltage protection: 24V : 30 ~ 36V, 48V: 59 ~ 66V shut off, AC recycle to re-start
Over temperature protection: Shut down output voltage, recovers automatically after temperaure goes down
Withstand time: I/P ~ O/P: 3KV, I/P ~ FG: 1.5KV, O/P ~ FG: 0.5KV, 1 minute
Working temperature: -20 ~ +45° C @ 100%, 60° C @ 50% load
Safety standard: UL 508, UK60950-1, TUV EN60950-1 approved
EMC standard EN55022 class B, EN61000-3-2, 3 ENV50204, EN61000-4-2,3,4,5,6,8,11, EN61000-6-2, EN61204-3
Connection: I/P: 4 poles, O/P: 6 poles screw DIN terminal
Dimensions: 276 x 125.2 x 100mm
Weight: 3.3 kg

Type No. Output Tol. R&N Efficiency
DRT -960-24 24V, 0 ~ 40A ±1% 80mV 91%
DRT -960-48 48V, 0 ~ 20A ±1% 80mV 92%

Click here to enquire about this product | Amalgen Homepage


Amalgen Technologies Pty Ltd
43 Anderson Road,
Mortdale NSW 2223 Australia
Phone: +61 2 9570 2855
Fax: +61 2 9580 5128
 
© 2007 All rights reserved. Amalgen Technologies Pty Ltd.