DRT-960 - 960W three phase DIN rail power
|
![]() |
| Specifications | |
| Input voltage: | 340 ~ 550 VAC ; 3 phase 4 wires |
| Output voltage: | Refer to table below |
| Inrush current: | Cold start, 50A |
| Adjustment range: | 24V : 24 ~ 28V, 48V : 48 ~ 55V |
| Overload protection: | 105% ~ 125% output constant current limiting shut off after 3 sec., AC recycle restart |
| Over voltage protection: | 24V : 30 ~ 36V, 48V: 59 ~ 66V shut off, AC recycle to re-start |
| Over temperature protection: | Shut down output voltage, recovers automatically after temperaure goes down |
| Withstand time: | I/P ~ O/P: 3KV, I/P ~ FG: 1.5KV, O/P ~ FG: 0.5KV, 1 minute |
| Working temperature: | -20 ~ +45° C @ 100%, 60° C @ 50% load |
| Safety standard: | UL 508, UK60950-1, TUV EN60950-1 approved |
| EMC standard | EN55022 class B, EN61000-3-2, 3 ENV50204, EN61000-4-2,3,4,5,6,8,11, EN61000-6-2, EN61204-3 |
| Connection: | I/P: 4 poles, O/P: 6 poles screw DIN terminal |
| Dimensions: | 276 x 125.2 x 100mm |
| Weight: | 3.3 kg |
| Type No. | Output | Tol. | R&N | Efficiency |
| DRT -960-24 | 24V, 0 ~ 40A | ±1% | 80mV | 91% |
| DRT -960-48 | 48V, 0 ~ 20A | ±1% | 80mV | 92% |
| Click here to enquire about this product | Amalgen Homepage |
|
Amalgen Technologies Pty Ltd 43 Anderson Road, Mortdale NSW 2223 Australia Phone: +61 2 9570 2855 Fax: +61 2 9580 5128 |
| © 2007 All rights reserved. Amalgen Technologies Pty Ltd. |