Aegis Specifications


Application AEGIS-HW AEGIS-PR AEGIS+
  3 Wire Grounded System 2 Wire Ungrounded System 1, 2, and 3 Pole Systems
Input Voltage, single phase 120, 220, 240 VAC, single phase 120, 220, 240 VAC 120, 208, 240, 400, 480, 600 V;
Wye, Delta, and International Systems
Amperage 3, 5, 10, 15 Amps 15 Amps 20, 30, 50, 75, 100 Amps
Frequency 50/60 Hz 50/60 Hz 50/60 Hz
Protection Modes L-N, L-G, N-G L-N, L-G, N-G L-N, L-G, and N-G modes (Wye system);L-L and L-G (Delta System)
MCOV 150, 275 V 150, 275 V 150, 275, 320, 420 V
Noise Attenuation:  
Normal Mode: 85 dB @ 100 kHz 75 dB @ 100 kHz 65 dB @ 100 kHz
Common Mode: 50 dB @ 5 MHz 50 dB @ 5 MHz 40 dB from 60 kHz to 5 MHz
Filter Bandwidth 10 kHz to 50 MHz 10 kHz to 50 MHz 10 kHz to 50 MHz
Total Peak Surge Current 39,000 Amps per phase 39,000 Amps per phase 80,000 Amps per phase
Operating Temperature -40 to +50 degrees C -40 to +50 degrees C -40 to +65 degrees C
Response Time Less than 1 nanosecond Less than 1 nanosecond Less than 1 nanosecond
Options Form C relay contacts Form C relay contacts Form C relay contacts; NEMA 3R/4X Container; Disconnect Switch; 40 kA or 160 kA
Agency Approvals UL 1449, UL 1283, CE, CSA UL 1363, UL 1449, UL 1283, UL 497A, CSA CE (pending), CSA (pending), UL 1449 (pending)