AEGIS+ Single and Three Phase Filters


Specifications
Input Voltages 120,208,240,347,380, 415,480 and 600
Single Phase, three Phase (Wye/Delta) 50/60 Hz
Current Capacity 20, 30, 50, 75 and 100 Amperes
Protection Modes L-N, L-G, N-G (Wye) and L-L, L-G (Delta)
Max Cont. Overvoltage 150, 275, 320 and 420 Volts (as appropriate)
Noise Attenuation
Normal Mode
Common Mode
 
65 dB at 100 kHz
40 dB from 60 kHz to 5 MHz
Filter Bandwidth 10 kHz to 50 MHz
Total Peak Surge Current 40kA/80kA/160kA per phase
Let Through Voltages L-N 120V Mode 240V Mode 277V Mode
Category C3 (10 kA)* <400 Volts <750 Volts <820 Volts
Category B3 Ringwave* <60 Volts <60 Volts <60 Volts
UL1449 Wave (3 kA) <330 Volts <650 Volts <710 Volts
Operating Temperature -40 to +65 Deg. Celsius
Diagnostics Indicator Lights
Case Style Surface mounting unfused exposed terminal metal enclosure
Protection Fuses/Breaker - inline
Dimensions 254 x 114 x 83 (single phase)
381 x 254 x 127 (three phase)
Options Monitoring Contacts
* Based on ANSI / IEEE C62.41,1991 and C62.45,1992

Ordering Guidelines