| Tycor PTY Filters
Tycor PTY Filters are designed for use at the incomming main switchboard and/or the first distribution board where a main or a sub main enters a building. These can be incorporated in the board or mounted very close to the board with leads kept as short, as possible. A very effective filtering system can be achieved with two PTY filters incorporated into the distribution network at each end of a sub main. |
![]() |
| Model No. | PTY - S2 | PTY - S | PTY - B | Magnum |
| Surge current per phase | 160 kA | 120 kA | 90 kA | 60 kA |
| Protection modes (Wye) | 7 | 7 | 7 | 7 |
| TVSS construction Matched MOV array |
Yes | Yes | Yes | Yes |
| TVSS construction Balanced "Surge Plane" |
Yes | Yes | Yes | Yes |
| UL1449 and UL1283 listed | Yes | Yes | Yes | Yes |
| CSA22.2 Certified | Yes | Yes | Yes | Yes |
| Repetitive withstand test ANSI/IEEE C3 (10kA) |
>3000 Surges |
>2500 Surges |
>1500 Surges |
>1500 Surges |
| Filter Attenuation (MIL-STD-220A) at 100 kHz |
55dB | 55dB | 40dB | 40dB |
| 200kAIC Internal Fusing | Yes | Yes | Yes | No |
| "Transient Switch" | Optional | Optional | Optional | No |
| "TRI_Monitor" | Standard | Standard | Optional | No |
| Diagnostic Package | SD | SD | Status indication |
Status indication |
| Optional Diagnostic Package |
ED or PD | ED or PD | SD, ED or PD | No |
| Dimensions | 413 x 362 x 159 |
413 x 362 x 159 |
324 x 158 x 108 |
324 x 158 x 108 |
| Diagnostic Package | Premium Diagnostics PD |
Enhanced Diagnostics ED |
Standard Diagnostics SD |
| Phase Status indicator lights | Yes | Yes | Yes |
| TVSS "TRI-Monitor" System | Yes | Yes | Yes |
| Trouble light (flashing alarm) | Yes | Yes | Yes |
| Remote monitoring | Yes | Yes | |
| Push-to-test feature | Yes | Yes | |
| Surge Counter | Yes | ||
| Audible Alarm | Yes |
|
Transient Switch™ Provides an Additional Performance Boost - This option enhances PTY Suppression Performance and acts like a trap door dor surges that exceed 1 Volt above the peak operating voltage. Benefits include 50% less stress on MOVs; a five fold increase of MTBF and the lowest system let through voltage possible. Surge Plane Technology - This specific TYCOR technology allows with careful matching of the MOVs for full utilisation of the MOV's surge capacity. TVSS "TRI-Monitor"™ System Monitors:
|
|
Ordering Guidelines
|
| Click here to enquire about this product | Amalgen Homepage |
|
Amalgen Technologies Pty Ltd 43 Anderson Road, Mortdale NSW 2223 Australia Phone: +61 2 9570 2855 Fax: +61 2 9580 5128 |
| © 2007 All rights reserved. Amalgen Technologies Pty Ltd. |